Evaluation unit NLSW75A for switch cabinet installation, flow monitoring with analog output (0 ... 10 V, 4 ... 20 mA)
Description
Description
Universal air flow monitor with analog output (0 ... 10 V & 4 ... 20 mA) for switch cabinet installation
✅ Large measuring range (0.1 ... 20 m/s), quick and easy commissioning
✅ Exemplary areas of application: Visualization and control of air flows in processes in the semiconductor and photovoltaic industry, exhaust air monitoring (e.g. drainage systems) and in HVAC applications
Evaluation unit NLSW75A for switch cabinet installation, flow monitoring with analog output (0 ... 10 V, 4 ... 20 mA) - 230 V AC is in stock and will be shipped as soon as it is available again

Availability for pickups could not be loaded
Specification
Specification
-
MediumGases
-
Device typeFlow evaluation unit for switch cabinet installation, or installation at the measuring point
-
Flow measuring range0.5 ... 30 m/s
-
Media temperature0 ... 70°C
-
DisplayLED (voltage & switching point)
-
Switching pointStepless adjustment (potentiometer)
-
Protection class evaluation unitIP20
-
Output signalSwitching output, analog output
-
Switching output specification1 changer
-
Signal output sensor breakRelay drops out
-
Signal output Sensor short circuitRelay drops out
-
Relay output specification1 changer
-
Housing materialPolycarbonate glass fiber reinforced (UL94V-0)
-
Housing materialPolycarbonate glass fiber reinforced (UL94V-0)
-
Housing dimensions120 mm x 75 mm x 73 mm
-
AssemblyDIN rail
-
Power supply24 V AC/DC ± 5%, 230 V AC ± 5%
-
Electrical connectionTerminal strip
-
Power consumption max3 VA
-
Recommended cable cross-section2.5 mm²
-
Current and contact load capacity250 VAC, 8 A, 2 kVA
-
Minimum switching capacity10 mA, 5 V DC
-
Ambient temperature-20... 50°C
-
CertificatesCE
-
ATEX certificationnone
-
SIL levelnone
-
Country of origin
-
Customs tariff number
-
HS Code