Compact flow monitor (incl. sensor) RLSW7 with relay output for monitoring liquid media
Description
Description
Flow monitors for water and air flows
Robust stainless steel sensor housing for industrial environments
Type tested by TÜV NORD in accordance with DIN EN 61010-1: 2011-07
Sensitive and infinitely adjustable switching point for both liquids (0.03 ... 3 m/s) and gases (0.5 ... 20 m/s)
With switching output (1 NO/ 1 NC)
Exemplary areas of application: Monitoring of air and water flows, cooling circuits with up to 30% glycol content, pump monitoring
Compact flow monitor (incl. sensor) RLSW7 with relay output for monitoring liquid media - 46 mm / 24 V AC/DC / G1/2-inch is in stock and will be shipped as soon as it is available again
Availability for pickups could not be loaded
TÜV type examination: Download
Operating instructions EN: Download
Operating instructions EN: Download
Specification
Specification
-
MediumLiquids, gases
-
Device typeCompact flow device
-
Device typeCompact device including sensor (permanently mounted)
-
Flow measuring rangeAir: 0.5 m/s ... 20 m/s , Water: 0.03 m/s ... 3 m/s
-
Displayyellow LED at flow velocities > switching point, green LED during operation
-
Switching pointStepless adjustment (potentiometer)
-
Protection class evaluation unitIP65
-
Sensor protection classIP67
-
Output signalSwitching output
-
Signal output sensor breakRelay drops out
-
Signal output Sensor short circuitRelay picks up on flow (changeover contact)
-
Immersion depth46, 48, 68, 150
-
Process connectionG1/2-inch, G1/4-inch
-
Housing materialUL94-V0, polyamide
-
Material sensorStainless steel, 1.4305
-
Compressive strength20 bar
-
Housing materialUL94-V0, polyamide
-
Housing dimensions56 mm x 84 mm x 80 mm
-
Power supply24 V AC/DC ±5%, 230 V AC ±6%
-
Electrical connection5 terminals (2.5 mm²)
-
Power consumption max3 VA at 24 V AC/DC, 4.5 VA at 230 V AC
-
Current and contact load capacity250 VAC, 6 A, 1.5 kVA
-
Minimum switching capacity10 mA/ 5 V DC
-
Ambient temperature-20 ... 60°C
-
Optimal run-in distance>5 DN
-
Optimal run-out distance>3 DN
-
Temperature gradient
-
CertificatesCE, Type-tested TÜV Nord according to DIN EN 61010-1 2011-07
-
Country of origin
-
Customs tariff number
-
HS Code
-
Pollution class