Compact flow monitor RLSW5 F3 with relay output
Description
Description
✅ Compact air flow monitoring with switching output (1 NO/1 NC) with TÜV type examination (in accordance with DIN EN 61010-1: 2011-07)
✅ Robust sensor design, high sensor protection class IP67, sensitive and fast air flow detection
✅ Reliable monitoring of gas flows, continuously adjustable from 0.1 ... 30 m/s
✅ Exemplary areas of application: Monitoring of heating coils, extraction systems, air curtain systems, dampers, fans and building services systems (DDC)
Compact flow monitor RLSW5 F3 with relay output - 50 mm / 230 V AC is in stock and will be shipped as soon as it is available again
Availability for pickups could not be loaded
TÜV type examination: Download
Operating instructions EN: Download
Operating instructions EN: Download
Delivery and shipping
Delivery and shipping
Immediately available from stock
Specification
Specification
-
MediumGases
-
Device typeCompact flow device
-
Device typeCompact device including sensor (permanently mounted)
-
Flow measuring range0,1 ... 30 m/s
-
Media temperature-20 ... 90°C
-
Displayyellow LED at flow velocities > switching point, green LED during operation
-
Switching pointStepless adjustment (potentiometer)
-
Protection class evaluation unitIP65
-
Sensor protection classIP67
-
Enclosure protection classIP65
-
Special featuresActivatable start-up delay 0 ... 60 s
-
Output signalSwitching output
-
Switching output specificationRelay picks up on flow (changeover contact)
-
Signal output sensor breakRelay drops out
-
Signal output Sensor short circuitRelay drops out
-
Relay output specificationRelay picks up on flow (changeover contact)
-
Immersion depth50 mm, 130 mm, 165 mm, 300 mm, 400 mm, 500 mm, Special lengths on request
-
Process connectionPG7, optional G1/2-inch, G1/4-inch by means of reducer
-
Housing materialPolyamide, UL94-V0
-
Material sensorMS58, nickel-plated (optional stainless steel available)
-
Compressive strength10 bar
-
Housing materialPolyamide, UL94-V0
-
Housing dimensions56 mm x 84 mm x 80 mm
-
Power supply24 V AC/DC ±5%, 230 V AC ±5%
-
Electrical connection5 terminals (2.5 mm²)
-
Power consumption max3 VA
-
Current and contact load capacity250 VAC, 6 A, 1.5 kVA
-
Minimum switching capacity10 mA, 5 V DC
-
Ambient temperature-20 ... 60°C
-
Optimal run-in distance>5 DN
-
Optimal run-out distance>3 DN
-
Temperature gradient
-
CertificatesCE, Type-tested TÜV Nord according to DIN EN 61010-1 2011-07
-
Country of origin
-
Customs tariff number
-
HS Code
-
Pollution class