Electromagnetic flowmeter FlowGuard® FT480 with heat and cold flow meter
Description
Description
✅ Calculation of the amount of heat in gigajoules
✅ Flow measurement from 0.06 to 12 m/s
✅ Bidirectional measurement with direction detection and empty conduit detection
With pulse output, analog signal (4-20 mA), HART and Modbus connection
✅ Different process connections and linings optimized for your process, with drinking water approval on request
✅ In special versions also suitable as heat meters with billing capability. MID-certified devices available on request
Optionally available up to protection class IP68 and therefore ideal for industrial use
✅ Min. temperature difference 3°C standard, 2°C possible on request
✅ Made for you and available at short notice within ~3 weeks
Electromagnetic flowmeter FlowGuard® FT480 with heat and cold flow meter - DN10 / thread / PFA is in stock and will be shipped as soon as it is available again

Availability for pickups could not be loaded
Specification
Specification
-
MediumLiquids
-
Device typeMagnetic inductive flow meter
-
Device typeCompact device, with remote evaluation unit (standard cable length 3 m)
-
Flow measuring range0.06 ... 12m/s, bidirectional measurement, max. (1/200)
-
Flow measurement accuracy≤0.5% of the measured value
-
Media temperatureCompact: max. 90°C (depending on version), Remote: max. 150°C (depending on version)
-
DisplayLCD display, 2×16 characters
-
Protection class evaluation unitStandard device (H - head) - IP65, Front device (F) - IP67, Panel device (P) - IP54
-
Sensor protection classIP65, IP67, IP68
-
Special featuresEmpty pipe detection DN15 ... DN600, Pressure loss negligible, Additional electrodes for earthing and detection of empty pipes
-
Temperature resolution0,5°C
-
Output signalPulse output, analog output, digital output
-
Signal output sensor break<3,5 mA
-
Process connectionSandwich (PN25 only), Flanged DIN (EN1092) - carbon or stainless steel, Thread (EN 10226-1) Food grade (DIN 11851 fitting, clamp)
-
Housing materialStainless steel, Steel ST37 (coated)
-
Material sensorStainless steel DIN 1.4571, Hastelloy C4, titanium, tantalum
-
Compressive strengthPN10, PN16, PN25, PN40
-
Housing materialStainless steel, Steel ST37 (coated)
-
DiameterDN10 ... 600 (other diameters on request)
-
Power supply24 VAC/ VDC with reverse polarity protection, 230 VAC (50/60 Hz), 110 VAC (60Hz), battery
-
Power consumption max9.6 VA
-
Ambient temperature0 ... 55°C
-
ZertifikateCE
-
SIL levelnone
-
Country of origin
-
Customs tariff number
-
HS Code
-
Reproducibility of the output signal0,2%