Evaluation unit NLSW75A Ex, flow monitoring for ATEX areas with analog output (0 ... 10 V, 4 ... 20 mA) and relay output
Description
Description
Air flow monitor for monitoring air flow in ATEX zones 1 and 2
2 associated Zener barriers included in the scope of delivery
With analog output (0 ... 10 V & 4 ... 20 mA), suitable for switch cabinet installation
Large measuring range (0.1 ... 20 m/s), quick and easy commissioning
Example areas of application: Monitoring of heating registers, air curtain systems, butterfly valves, fans, DDC, industrial furnaces, granulate dryers
Evaluation unit NLSW75A Ex, flow monitoring for ATEX areas with analog output (0 ... 10 V, 4 ... 20 mA) and relay output - 230 V AC is in stock and will be shipped as soon as it is available again
Availability for pickups could not be loaded
Specification
Specification
-
MediumGases
-
Device typeFlow evaluation unit for switch cabinet installation, or installation at the measuring point
-
Flow measuring range0.5 ... 20 m/s
-
Media temperature0 ... 60°C
-
DisplayLED (voltage & switching point)
-
Switching pointStepless adjustment (potentiometer)
-
Protection class evaluation unitIP20
-
Output signalSwitching output, analog output
-
Switching output specification1 changer
-
Signal output sensor breakRelay drops out
-
Signal output Sensor short circuitRelay drops out
-
Relay output specification1 changer
-
Housing materialPolycarbonate glass fiber reinforced (UL94V-0)
-
Housing materialPolycarbonate glass fiber reinforced (UL94V-0)
-
Housing dimensions120 mm x 75 mm x 73 mm
-
AssemblyDIN rail, outside the ATEX zone
-
Power supply24 V DC ± 5%, 24 V AC ± 5%, 230 V AC ± 5%
-
Electrical connectionTerminal strip
-
Power consumption max5 VA
-
Recommended cable cross-section2.5 mm²
-
Current and contact load capacity250 VAC, 6 A, 1.5 kVA
-
Minimum switching capacity10 mA, 5 V DC
-
Ambient temperature-20 ... 50°C
-
CertificatesCE
-
ATEX certificationZone 1, zone 2
-
Country of origin
-
Customs tariff number
-
HS Code